Formulas for DC, single-phase and three-phase power
In a DC circuit, power is simply voltage times current: P = V × I. A 12 V load drawing 5 A uses 60 W.
AC circuits have three related power quantities. Apparent power S (volt-amperes, VA) is voltage times current. Real power P (watts, W) is the part that does work, P = S × PF, where PF is the power factor. Reactive power Q (volt-amperes reactive, var) is the part that flows back and forth to charge motor windings and capacitors: Q = √(S² − P²).
For a balanced three-phase load measured with line-to-line voltage, multiply by √3 (about 1.732): S = √3 × V × I and P = √3 × V × I × PF.
| Circuit | Real power (W) | Current (A) |
|---|---|---|
| DC | P = V × I | I = P ÷ V |
| AC single-phase | P = V × I × PF | I = P ÷ (V × PF) |
| AC three-phase | P = √3 × V × I × PF | I = P ÷ (√3 × V × PF) |
Worked example: kW to amps on a three-phase supply
A 10 kW three-phase motor load runs at 400 V line-to-line with a power factor of 0.85. Current I = 10,000 W ÷ (1.732 × 400 V × 0.85) = 17.0 A.
The apparent power is 10 kW ÷ 0.85 = 11.8 kVA, which is what the supply cable and breaker actually have to carry.
Why kVA and kW differ
Generators, transformers and UPS units are rated in kVA because their heating depends on current, whatever the power factor. The load's useful output is in kW. With a power factor of 1 the two are equal; with 0.8, a 100 kVA transformer can supply only 80 kW.
If you do not know the power factor, a resistive load such as a heater or incandescent lamp is 1. For motors and electronic supplies use the nameplate or datasheet value rather than guessing.